INSERT-AIR-SYSTEMS
NOTES: 1. ALL CONTACTS IN THE DIAGRAM ARE SHOWN WITH THE SYSTEM DE-ENERGIZED AT ATMOSPHERIC PRESSURE. SW# 1 CONTACT 1-2 : CLOSES AT 0.25 PSIG & ABOVE. CONTACT 1-3 : CLOSES AT A PRESSURE OF 0.25 PSIG OR BELOW, SENDING AN ALARM, IF MONITORED. SW# 2 CONTACT 6-4 : CLOSES AT 5.5 PSIG & BELOW. CONTACT 6-5 : CLOSES AT A PRESSURE OF 5.5 PSIG OR ABOVE, SENDING AN ALARM, IF MONITORED. SW# 3 CONTACT BLU-BLK : N.C., OPENS AT 200.0 PSIG CONTACT RED-BLK : N.O., CLOSES AT 200.0 PSIG
NO LO C NO HI TRANS. TANK ALARMS 1 2 3
NITROGEN STORAGE ALARM
TRANS. TANK STOR. TANK
L1 N 120 N G HEATER SUPPLY POWER (VAC)
(4-20mA)
(4-20mA)
NO C NC + - + -
6 7
9 10 11 12 13 14 15
8
4 5
GR
GR
BLK
RED
12
1 1 BLK BLK
5
SW# 2
4
6
2
RED
BLK
BLU
NO C NC
NC C NO
5.5 PSI
5.5 PSI
2
PS1
SW# 3
HIGH PRESS
2 1 3
ALARM ENABLE SWITCH
BLIZZARD 60W PTC HEATER
.25 PSI .25 PSI
NO C NC
LOW PRESS
PG1
SW# 1
WIRING DIAGRAM
SHEET 2 OF 2
Made with FlippingBook flipbook maker